| Model | DSG-10602 |
|---|
| Professional analyzer for testing power grid quality. |
| Test function | Real-time waveform display (4 voltage channels / 4 current channels); true RMS value of voltage and current; DC component of voltage; current and voltage peak; maximum/minimum value of current and voltage within a given time; phasor diagram display; harmonic measurement on each phase up to the 50th; the histogram shows the harmonic ratio of each phase current and voltage; total harmonic distortion (THD) calculation; active/reactive/apparent power value and total value for each phase; active/reactive/apparent electrical energy value for each phase and total value for each phase; transformer K-factor calculation; displacement COSΦ and power factor (PF) calculation; flicker calculation; three-phase imbalance calculation (voltage and current) |
|---|
| Capture and monitoring functions | Instant capture of changes in grid voltage and current parameters, including voltage and current fluctuations, voltage and current swells, sags, short-term interruptions, transient overvoltage, impulse current and instantaneous current and voltage distortion. The device can store up to 150 sets of transient waveforms at once |
|---|
| Inrush current monitoring | It can monitor the circuit's inrush current and the starting current of electrical equipment, which is useful for correct planning of installed power. It can display the rise/fall curve of the effective value during start-up, the envelope curve of the starting current, 4-channel current and 4-channel voltage waveform. After start-up, about 100 seconds can be recorded, storing all instantaneous current and voltage values and waveform curves in each cycle within 100 seconds |
|---|
| Logging and storage function | All test parameters of the basic test functions (Urms, Uthd, Ucf, Uunb, Hz, Vrms, Vthd, Vcf, Vunb, PST, Arms, Athd, Acf, Aunb, KF, W, VAR, VA, PF, COSΦ, TANΦ), voltage harmonics up to 50th, current harmonics up to 50th, a total of 123 parameters to record, and creating a trend diagram, logging data for a long time as needed. (Selecting 20 parameters to record simultaneously every second, about 300 days can be recorded) |
|---|
| Screenshot function | A screenshot can be taken on any test page to store the current screen image, automatically recording the time and test status, such as saving voltage and current waveforms, harmonic histograms, phasor diagrams, etc. Up to 60 screenshots can be saved at once |
|---|
| Communication function | Via USB communication with a computer, the monitoring software can display the power quality analysis waveform and test in real time, and can read the detected and captured transient waveform, trend records, alarm list, test screenshot, etc. |
|---|
| Settings function | The user can set the time and date, display contrast and brightness, and the color of each phase line on the device; the device's connection mode and grid type can be set; a different current clamp and a different voltage probe transformation ratio can be selected. Menu in English |
|---|
| Capacitance measurement | 400-590Ω |
|---|
| Resistance measurement range | 200Ω-395Ω |
|---|
| Inductance measurement range | 900Ω-1200Ω |
|---|
| Direct mains connection | Available |
|---|
| Battery | Up to 8 hours of operation |
|---|
| Screen size | “5.6 |
|---|
| Height | 285 mm |
|---|
| Width | 85 mm |
|---|
| Depth | 58 mm |
|---|
| Accessories | Carrying case |
|---|